Manual Operation
3-55
3.2.4.5 External Output
The setting of DI1 and DI2 function needs to work with external Analog Interface as Figure
3-82 shows.
Figure 3-82
1. Remote INHIBIT function allows users to remotely turn-off power supply. Logic: Low
sets Remote INHIBIT to enable, the power supply’s ON/OFF is still controlled by .
When the Pin 6 and Pin18 (_INHIBIT) of ANALOG INTERFACE are triggered in low
level that equals to tap “ ” on the front panel and set OUTPUT = OFF. The DC
power supply will shut down and sends out a protection signal (in this case the
button will be off), and Pin6 and Pin18 (_INHIBIT) of ANALOG INTERFACE cannot be
used to release the protection.
2. When protection occurs to REMOTE INHIBIT the main page will appear the protection
message as Figure 3-83 shows.
3. Tap
Confirm
to return to the main page.