CRS-300 1:10 Redundancy Switch MN/CRS300.IOM
Installation Revision 19
2–3
PROPER AIR VENTILATION IS REQUIRED.
o Air temperature inside the rack enclosure should
NEVER
exceed 50
°
C (122
°
F).
o Since the Switch itself is relatively passive, no additional clearance is needed
between it and the nearest modem.
o The CRS-300
CANNOT
have rack slides mounted to the sides of the chassis
air flow must not be impeded. Comtech EF Data recommends that an
alternate method of support is provided within the rack, such as standard rack
shelves, as needed.
o Make sure there is adequate clearance inside the enclosure, especially at the
sides, for air ventilation. In a rack system where there is high heat discharge,
provide forced-air cooling with top- or bottom-mounted fans or blowers.
For information about custom rack enclosures, contact Comtech EF Data Product
Support.