Protection Functions
166 PRS-7367
Uca2>Bus_Live_VolANA
SIG
AND_Bus2_Live_Vol
Ubc2>Bus_Live_VolANA
Uab2>Bus_Live_VolANA
&
Uca1>Bus_Live_VolANA
SIG
AND_Bus1_Live_Vol
Ubc1>Bus_Live_VolANA
Uab1>Bus_Live_VolANA
&
Uca2>Bus_Live_VolANA
SIG
OR_Bus2_Live_Vol
Ubc2>Bus_Live_VolANA
Uab2>Bus_Live_VolANA
1
Uca1>Bus_Live_VolANA
SIG
OR_Bus1_Live_Vol
Ubc1>Bus_Live_VolANA
Uab1>Bus_Live_VolANA
1
Figure 3.34-2 Diagram of busbar live voltage logic
2) "Busbar dead voltage” means Uab, Ubc and Uca as phase to phase voltage of busbar are
all less than busbar dead voltage setting value. Busbar dead voltage conditions of Uab,
Ubc and Uca must be satisfied meanwhile in case of 1 or 2 phase line-break of PT of
operational power supply.
Uca1<Bus_Dead_VolANA
SIG
Bus1_Dead_Vol
Ubc1<Bus_Dead_VolANA
Uab1<Bus_Dead_VolANA
&
Uca2<Bus_Dead_VolANA
SIG
Bus2_Dead_Vol
Ubc2<Bus_Dead_VolANA
Uab2<Bus_Dead_VolANA
&
Figure 3.34-3 Diagram of busbar dead voltage logic
3) "Incoming line live voltage means someone phase voltage (or line voltage) is greater than
incoming line live voltage setting value. If there's no incoming line PT on site, incoming
line normal voltage criterion could be disabled through L1_Vol_Ena and L2_Vol_Ena