MAN MACHINE INTERFACE
PRS-7367 305
1- User
In this section user can easily set relay operator setting like operator 1 or 2 or guest 1. See below
table 7.3.5 and figure 7.3.27:
Table 7.3-3 User setting detail
User operator selection options
The manufacturer user has all the configuration functions of
access to device setting. At the same time, only the
manufacturer's user has the access to hide, read, and write
(display) to the logical device LD, logical component LN and
logical component data item DO of 61850 protocol and logical
picture subgraph. Therefore, as to realize the manufacturer's
basic configuration of the device and not be suitable for
opening up the correlation. The content settings for users are
hidden and should not be opened to users to modify, but the
contents they need to view are set to read-only.
Note!
Non of other users have access to this setting function except
manufacturer.
The engineering user staff account has all the general access
of configuration (view and modification) functions of the
configuration tool, including drawing logical pictures, main
wiring diagrams etc.
Note!
In this user login section, user cannot create an account
configuration of the configuration device setting.
1) The engineering account can only view and modify
its own password.
2) This account automatically withdraws or logoff
after 30 minutes without operation.
The operator user account, generally it can only view the
configuration of the device, the logical picture, wiring diagram
and the logical device component. In this section user can’t
create and modify any of its configuration, such as moving the
map element position and deleting port association etc.
Guest user account is only for visitors. In this section user
have no rights to change or view any kind of configuration
information.