deTaIled daTa PoInT InformaTIon
Actual RPM
Keypad Menu Path:
No Keypad Equivalent
This variable indicates the actual speed of the compressor. (I118 & I122)
Measurement Units Data Type Valid Range Default Value
Revolutions per Minute BACnet: RPM BACnet: Real BACnet: 0–-32678 NA
BACnet
Compressor #1
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 56 Present Value 85
Object Name
Comp1ActualRPM
Compressor #2
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 60 Present Value 85
Object Name
Comp2ActualRPM
LONWORKS
No LONWORKS equivalent.
Capacity Limit
Keypad Menu Path:
No Keypad Equivalent
Capacity Limit is a measure of the ratio of operating capacity to full capacity expressed in percent. This
LONWORKS variable sets a default value for the capacity limit of the chiller, unless the conguration
property, nciDefaults = 1 (See Default Values on page 59). If nciDefaults = 1, the default values are
the values specied during manufacturing. The capacity limit value is not the nominal capacity limit of
the Chiller. Refer to the appropriate Operating Manual for suitable variable values.
Measurement Units Data Type Valid Range Default Value
Percent of maximum capacity NA
LONWORKS: Fixed-Point
Scalar signed long
0% to 160%. See Below
LONWORKS
Default Value
100% The chiller object uses the conguration value of nciCapacityLim on power-up or loss of communication unless
the conguration parameter nciDefaults = (see Default Values on page 59).
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT Index
nciCapacityLim
(conguration)
Chiller 81 two bytes SCPTlimitChlrCap 81