deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 79 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Oil Feed Pressure
Keypad Menu Path:
Menu
\View
\Comp (3)
Measurement Units Data Type Valid Range Default Value
Pressure
BACnet: psi
LONWORKS: kPa
BACnet: Real
LONWORKS: Fixed-Point
Scalar signed long
BACnet: -22592–22591 psi
LONWORKS:
-3,276.8…3,276.7 kPa
NA
BACnet
Compressor Select
This output network variable indicates the current compressor oil feed pressure. There is a separate output for each compressor.
See Compressor Select on page 43. (A32)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 19 Present Value 85
Object Name
OilFeedPressure
Compressor #2
This variable indicates the current oil feed pressure for compressor 2. Not available on all chiller models. (A100)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 81 Present Value 85
Object Name
Comp2OilFeedPress
LONWORKS
Variable Details
This output network variable indicates the current compressor oil feed pressure. There is a separate output for each compressor.
See Compressor Select on page 43. (A32)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoOilFeedPress Proprietary press 30 two bytes

Table of Contents

Other manuals for Daikin MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech II and is the answer not in the manual?

Daikin MicroTech II Specifications

General IconGeneral
BrandDaikin
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals