deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 45 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Compressor Status
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the number status of the compressor.
Measurement Units Data Type Valid Range Default Value
Event Count NA
BACnet: Real
LONWORKS: Fixed Point
Scalar - unsigned long
0–31 NA
BACnet
Compressor Select
This output network variable indicates the compressor status of the compressor selected with Compressor Select on page 43. (I44)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 123 Present Value 85
Object Name
CompressorStatus
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Compressor #2
This output network variable indicates the compressor status of the compressor 2. (I105)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 91 Present Value 85
Object Name
Comp2Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Compressor #3
This output network variable indicates the compressor status of the compressor 3. (I108)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 99 Present Value 85
Object Name
Comp3Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown