deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 63 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Evaporator Leaving Water Temperature for Unit
Keypad Menu Path:
Menu
\View
\Unit Water
OR
Menu
\View
Comp (2)
This output network variable indicates the current temperature of the evaporator leaving chilled water. (A6)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 2 Present Value 85
Object Name
LvgEvapWaterTempUnit
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoLvgCHWTemp Chiller temp_p 105 two bytes