deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 55 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Condenser Saturated Refrigerant Temperature
Keypad Menu Path:
Menu
\Unit
\Refrigerant (1)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Compressor Select
This output network variable indicates the current saturated refrigerant temperature in the condenser. There is a separate output for
each compressor. See Compressor Select on page 43. (A20)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 17 Present Value 85
Object Name
CondSatTemp
Compressor #2
This variable indicates the current saturated refrigerant temperature in the condenser for compressor 2. Not available on all chiller
models. (A92)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 73 Present Value 85
Object Name
Comp2CondSatTemp
LONWORKS
Variable Details
This output network variable indicates the current saturated refrigerant temperature in the condenser. There is a separate output for
each compressor. See Compressor Select on page 43. (A20)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size Data Type
nvoSatCndRefTemp Proprietary temp_p 105 two bytes
Fixed Point Scalar
signed long