deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 77 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Minimum RPM
Keypad Menu Path:
No Keypad Equivalent
This output data point indicates the minimum (surge) RPM. This is the speed the Turbocor compressor
calculates is the minimum safe operating speed above onset of stall. (I119 & I123)
Measurement Units Data Type Valid Range Default Value
Revolutions per Minute BACnet: RPM BACnet: Real BACnet: 0–32678 NA
BACnet
Compressor #1
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 57 Present Value 85
Object Name
Comp1MinRPM
Compressor #2
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 61 Present Value 85
Object Name
Comp2MinRPM
LONWORKS
No LONWORKS equivalent.
Minimum Send Time
Keypad Menu Path:
No Keypad Equivalent
This conguration network parameter controls the minimum period of time that expires before objects
can be retransmitted.
Measurement Units Data Type Valid Range Default Value
Elapsed Time seconds
BACnet: Unsigned Integer
LONWORKS: Fixed Point
Scalar - unsigned long
0–6553.4 sec 0 (no automatic update)
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT Index
nciMinSendTime Chiller time_sec 107 two bytes SCPT_minSendTime 52