deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 85 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Pump Select
Keypad Menu Path:
No Keypad Equivalent
This input network variable selects which pump (Number 1 or Number 2) supplies the data. The
controller returns the information for the appropriate Condenser or Evaporator pump. You must rst
select a pump and then interrogate the selected pump. See Condenser Pump Run Hours on page 53
and Evaporator Pump Run Hours on page 65. (D19)
Measurement Units Data Type Valid Range Default Value
Event Count NA
BACnet: Unsigned Integer
LONWORKS: structure
See Below
BACnet : 1 = Pump No. 1
LONWORKS: 0 = Pump No. 1
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Output 14 47 Present Value 85
Object Name
PumpSelect
Property Values
1 = Pump #1
2 = Pump #2
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nviPumpSelect Proprietary Switch 95 two bytes
Structure
typedef struct {
unsigned value;
signed state;
} SNVT_switch;
Valid Range
Value Field unused
State Field 0 Pump No. 1
1 Pump No. 2