ED 15062-7 • MICROTECH II CHILLER CONTROLLER 70 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Heat Recovery Entering Water Temperature
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the current temperature of the water entering the heat recovery
section. (A22)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS:-40°–118°C
NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 5 Present Value 85
Object Name
HeatRecEntWaterTemp
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoEntHRWTemp Proprietary temp_p 105 two bytes
Heat Recovery Leaving Water Temperature
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the current temperature of the water leaving the heat recovery
section. (A23)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS:-40°–118°C
NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 6 Present Value 85
Object Name
HeatRecLvgWaterTemp
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoLvgHRWTemp Proprietary temp_p 105 two bytes