deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 51 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Condenser Flow Switch Status
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the status of the water ow through the condenser. (D8)
Measurement Units Data Type Valid Range Default Value
Flow State NA
BACnet: Enumerated
LONWORKS: Structure
See Below NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 35 Present Value 85
Object Name
CondWaterFlowStatus
Property Values
0 = No Flow(Inactive)
1 = Flow(Active)
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoCndWFlow Proprietary switch 95 two bytes
Structure
typedef struct {
unsigned value;
signed state;
} SNVT_switch;
Valid Range
Value Field unused
State Field 0 No Flow
1 Flow