ED 15062-7 • MICROTECH II CHILLER CONTROLLER 30 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Chiller Mode Output
Keypad Menu Path:
No Keypad Equivalent
This output data point indicates the current operating mode of the chiller. (I19)
Measurement Units Data Type Valid Range Default Value
HVAC Mode NA
BACnet: Unsigned Integer
LONWORKS: Fixed Point
Scalar - unsigned long
See Below NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 44 Present Value 85
Object Name
ActiveMode
Property Values
1. ICE
2. COOL
3. HEAT
LONWORKS
The LONWORKS equivalent of this data point is part of the Chiller Status network output variable (see page 33).
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoChillerStat Chiller chlr_status 127 3 bytes