ED 15062-7 • MICROTECH II CHILLER CONTROLLER 38 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Compressor Percent RLA
Keypad Menu Path:
No Keypad Equivalent
Measurement Units Data Type Valid Range Default Value
Percent RLA Percent
BACnet: Real
LONWORKS: Fixed-Point
Scalar signed long
BACnet: 0–160%
LONWORKS:
-163.840–163.830%
NA
BACnet
Compressor Select
This output network variable indicates the current motor current for the compressor motor of the compressor selected with
Compressor Select on page 43. (A25)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 24 Present Value 85
Object Name
CompMotorCurrentPercent
Compressor #2
This variable indicates the current motor current for compressor 2. (A94)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 75 Present Value 85
Object Name
Comp2CurrentPercent
Compressor #3
This variable indicates the current motor current for compressor 3. (A108)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 94 Present Value 85
Object Name
Comp3CurrentPercent
Compressor #4
This variable indicates the current motor current for compressor 4. (A113)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 102 Present Value 85
Object Name
Comp4CurrentPercent
Compressor #5
This variable indicates the current motor current for compressor 5. (A118)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 110 Present Value 85
Object Name
Comp5CurrentPercent