deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 57 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Condenser Water Pump Status
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates whether the selected pump has been commanded ON or OFF.
See Pump Select on page 85. (D31)
Measurement Units Data Type Valid Range Default Value
Flow State NA
BACnet: Enumerated
LONWORKS: Structure
See Below NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 37 Present Value 85
Object Name
CondPumpState
Property Values
0 = Off (Inactive)
1 = On (Active)
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoCndWPump Proprietary Switch 95 two bytes
Structure
typedef struct {
unsigned value;
signed state;
} SNVT_switch;
Valid Range
Value Field unused
State Field 0 Pump Commanded Off
1 Pump Commanded On