deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 27 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Chiller Enable
Keypad Menu Path:
No Keypad Equivalent
This LONWORKS conguration variable sets the default power-up and restart mode of the chiller,
unless the conguration parameter nciDefaults = 1 (See Default Values on page 59). If nciDefaults =
1, the default values are the values specied during manufacturing. Refer to the appropriate Operating
Manual for suitable variable values.
Measurement Units Data Type Valid Range Default Value
Chiller State NA LONWORKS: structure Enumerated See Below
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT_ Index
nciChillerEnable Chiller switch 95 two bytes SCPTpwrUpState 73
Default Value
0 = Request Chiller Off
The chiller object uses the conguration value of nciChillerEnable on power-up or loss of communication unless the conguration
parameter nciDefaults =1 (See Default Values on page 59).
Structure
typedef struct {
unsigned value;
signed state;
} SNVT_switch;
Valid Range
Value Field unused
State Field 0 Request Chiller Off
1 Request Chiller Auto (run)
0xff Invalid

Table of Contents

Other manuals for Daikin MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech II and is the answer not in the manual?

Daikin MicroTech II Specifications

General IconGeneral
BrandDaikin
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals