deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 81 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Oil Sump Pressure
Keypad Menu Path:
No Keypad Equivalent
Measurement Units Data Type Valid Range Default Value
Pressure
BACnet: psi
LONWORKS: kPa
BACnet: Real
LONWORKS: Fixed-Point
Scalar signed long
BACnet: -22592–22591 psi
LONWORKS:
-3,276.8…3,276.7 kPa
NA
BACnet
Compressor Select
This output network variable indicates the current compressor oil sump pressure. There is a separate output for each compressor.
See Compressor Select on page 43. (A33)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 20 Present Value 85
Object Name
OilSumpPressure
Compressor #2
This variable indicates the current compressor oil sump pressure for compressor 2. Not available on all chiller models. (A101)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 82 Present Value 85
Object Name
Comp2OilSumpPress
LONWORKS
Variable Details
This output network variable indicates the current compressor oil sump pressure. There is a separate output for each compressor.
See Compressor Select on page 43. (A33)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoOilSumpPress Proprietary press 30 two bytes