deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 75 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Liquid Line Refrigerant Temperature
Keypad Menu Path:
Menu
\View
\Unit \Refrg (2)
Liquid Line=
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Compressor Select
This output network variable indicates the current liquid line refrigerant temperature. There is a separate output for each
compressor/circuit. See Compressor Select on page 43. (A36)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 11 Present Value 85
Object Name
LiquidLineTemp
Compressor #2
This variable indicates the current liquid line refrigerant temperature for compressor 2. Not available on all chiller models. (A104)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 85 Present Value 85
Object Name
Comp2LiqLineTemp
LONWORKS
Variable Details
This output network variable indicates the current liquid line refrigerant temperature. There is a separate output for each
compressor/circuit. See Compressor Select on page 43. (A36)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoLiquLineTemp Proprietary temp_p 105 two bytes