deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 53 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Condenser Pump Run Hours
Keypad Menu Path:
No Keypad Equivalent
NOTE: Value returned must be multiplied by 10 to give run hours.
Measurement Units Data Type Valid Range Default Value
Event Count NA
BACnet: Real
LONWORKS: Fixed-Point
Scalar signed long
0–65,535 NA
BACnet
Pump Select
This output network variable indicates the number of hours (x10) that the selected condenser pump motor has been turned on. See
Pump Select on page 85. (I48)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 28 Present Value 85
Object Name
CondPumpOperHours
Pump #2
This output network variable indicates the number of hours (x10) that the selected condenser pump 2 has been turned on. Not
available on all chiller models. (I104)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 90 Present Value 85
Object Name
CondPmp2Hrs
LONWORKS
Variable Details
This output network variable indicates the number of hours (x10) that the selected condenser pump motor has been turned on. See
Pump Select on page 85. (I48)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoCondPumpHrs Proprietary count 8 two bytes