ED 15062-7 • MICROTECH II CHILLER CONTROLLER 28 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Chiller Limited
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the main running mode and states of the Chiller. The Limited
network variable indicates whether conditions exist that prevent the chiller from reaching setpoint. (D6)
Measurement Units Data Type Valid Range Default Value
Status NA
BACnet: Enumerated
LONWORKS: Structure
See Below NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 39 Present Value 85
Object Name
ChillerLimited
Property Values
0 = Not Limited(Inactive)
1 = Limited(Active)
LONWORKS
The LONWORKS equivalent of this data point is part of the Chiller Status network variable output (see page 33).
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoChillerStat Chiller chlr_status 127 3 bytes
Chiller Local/Remote
Keypad Menu Path:
No Keypad Equivalent
The Local/Remote network variable indicates whether the chiller is in local control or allowed to be
controlled remotely over the network. (D5)
Measurement Units Data Type Valid Range Default Value
Mode NA
BACnet: Enumerated
LONWORKS: Structure
See Below NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 38 Present Value 85
Object Name
ChillerLocalRemote
Property Values
0 = Remote
1= Local
LONWORKS
The LONWORKS equivalent of this data point is part of the Chiller Status network output variable (see page 33).
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size Data Type
nvoChillerStat Chiller chlr_status 127 3 bytes Structure