deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 61 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Evaporator Entering Water Temperature
Keypad Menu Path:
Menu
\View
\Unit
\Water
This output attribute indicates the temperature of the evaporator entering water temperature. (A4)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40–245°F
LONWORKS: -40°–118°C
NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 1 Present Value 85
Object Name
EntEvapWaterTemp
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoEntChwTemp Chiller temp_p 105 two bytes