deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 37 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Compressor #6
This variable indicates the current compressor amperes of compressor 6. (A124)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 117 Present Value 85
Object Name
Comp6Current
LONWORKS
Variable Details
This output network variable indicates the current compressor amperes of the compressor selected with Compressor Select on
page 43. (A26)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoCurrent Proprietary amp 1 two bytes
Compressor Discharge Temperature
Keypad Menu Path:
Menu
\View
\Comp (5)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -460°–621°F
LONWORKS:
-273.17°–327.66°C
NA
BACnet
Compressor Select
This output network variable indicates the current compressor refrigerant temperature of the compressor selected with Compressor
Select on page 43. (A19)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 18 Present Value 85
Object Name
DischargeTemp
Compressor #2
This variable indicates the current compressor refrigerant temperature of compressor 2. Not available on all chiller models. (A91)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 Present Value 85
Object Name
Comp2DischargeTmp
LONWORKS
Variable Details
This output network variable indicates the current compressor refrigerant temperature of the compressor selected with Compressor
Select on page 43. (A19)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoCompDisTemp Proprietary temp_p 105 two bytes