EasyManuals Logo

Daikin MicroTech II Installation And Maintenance Manual

Daikin MicroTech II
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #59 background imageLoading...
Page #59 background image
deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 59 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Default Values
Keypad Menu Path:
No Keypad Equivalent
This conguration network parameter determines which set of values is used on power up and
communication failure. The choice is the stated default values or a list of manufacturer specied values.
This is used for the following conguration network variables: (D10)
Chiller Enable
Capacity Limit
Cool Setpoint
Heat Setpoint
Mode
Measurement Units Data Type Valid Range Default Value
Chiller State NA LONWORKS: structure Enumerated 0 = Use Default Values
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT Index
nciDefaults Chiller switch 95 two bytes
SCPT_
DefaultBehavior
71
Structure
typedef struct {
unsigned value;
signed state;
} SNVT_switch;
Valid Range
Value Field unused
State Field 0 Use Default Values
1 Use Manufacturer-Specied Values

Table of Contents

Other manuals for Daikin MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech II and is the answer not in the manual?

Daikin MicroTech II Specifications

General IconGeneral
BrandDaikin
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals