deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 59 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Default Values
Keypad Menu Path:
No Keypad Equivalent
This conguration network parameter determines which set of values is used on power up and
communication failure. The choice is the stated default values or a list of manufacturer specied values.
This is used for the following conguration network variables: (D10)
Chiller Enable
Capacity Limit
Cool Setpoint
Heat Setpoint
Mode
Measurement Units Data Type Valid Range Default Value
Chiller State NA LONWORKS: structure Enumerated 0 = Use Default Values
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT Index
nciDefaults Chiller switch 95 two bytes
SCPT_
DefaultBehavior
71
Structure
typedef struct {
unsigned value;
signed state;
} SNVT_switch;
Valid Range
Value Field unused
State Field 0 Use Default Values
1 Use Manufacturer-Specied Values