ED 15062-7 • MICROTECH II CHILLER CONTROLLER 68 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Evaporator Water Flow Rate
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the current evaporator water ow rate. (A18)
Measurement Units Data Type Valid Range Default Value
Flow Volume
BACnet: GPM
LONWORKS: L/S
BACnet: Real
LONWORKS: Fixed Point
Scalar unsigned long
BACnet: 0–65,534
LONWORKS: 0–65,534
NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 49 Present Value 85
Object Name
EvapWaterFlowRate
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoEvapFlowRate Proprietary ow 15 two bytes