deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 83 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Outdoor Air Temperature
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the current outdoor air temperature. (A39)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°– 118°C
NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 10 Present Value 85
Object Name
OutdoorAirTemp
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoOutdoorTemp Proprietary temp_p 105 two bytes