ED 15062-7 • MICROTECH II CHILLER CONTROLLER 78 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Motor Cavity Temperature
Keypad Menu Path:
No Keypad Equivalent
This output data point indicates the current temperature of the compressor’s motor stator cavity. (A85 &
A105)
Measurement Units Data Type Valid Range Default Value
Temperature BACnet: °F BACnet: Real BACnet: -4°–212°F NA
BACnet
Compressor #1
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 65 Present Value 85
Object Name
Comp1MotorCavityTmp
Compressor #2
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 86 Present Value 85
Object Name
Comp2MotorCavityTmp
LONWORKS
No LONWORKS equivalent.