ED 15062-7 • MICROTECH II CHILLER CONTROLLER 42 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Compressor Run Hours
Keypad Menu Path:
Menu
\View
\Compressor
NOTE: Value returned must be multiplied by 10 to give run hours.
Measurement Units Data Type Valid Range Default Value
Event Count Hours
BACnet: Real
LONWORKS: Float Type
unsigned long
0–65,535 NA
BACnet
Compressor Select
This output network variable indicates the number of hours (x10) that the compressor motor of the compressor selected with
Compressor Select on page 43. (I46)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 26 Present Value 85
Object Name
CompHours
Compressor #2
This variable indicates the number of hours (x10) for compressor 2. Not available on all chiller models. (I107)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 93 Present Value 85
Object Name
Comp2Hours
Compressor #3
This variable indicates the number of hours (x10) for compressor 3. Not available on all chiller models. (I110)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 101 Present Value 85
Object Name
Comp3Hours
Compressor #4
This variable indicates the number of hours (x10) for compressor 4. Not available on all chiller models. (I113)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 109 Present Value 85
Object Name
Comp4Hours
LONWORKS
This output network variable indicates the number of hours (x10) that the compressor motor of the compressor selected with
Compressor Select on page 43. (I46)
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoCompHrs Proprietary count 8 two bytes

Table of Contents

Other manuals for Daikin MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech II and is the answer not in the manual?

Daikin MicroTech II Specifications

General IconGeneral
BrandDaikin
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals