EasyManuals Logo

Daikin MicroTech II Installation And Maintenance Manual

Daikin MicroTech II
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 41 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Compressor #6
This variable indicates the current power for the compressor motor of compressor 6. It is available via BACnet only.(A123)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 118 Present Value 85
Object Name
Comp6Kilowatts
LONWORKS
Variable Details
This output network variable indicates the current power for the compressor motor of the compressor selected with Compressor
Select on page 43. (A27)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoKilowattts Proprietary power_kilo 28 2 bytes

Table of Contents