ED 15062-7 • MICROTECH II CHILLER CONTROLLER 44 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Compressor Starts
Keypad Menu Path:
Menu
\View
\Compressor
Measurement Units Data Type Valid Range Default Value
Event Count NA
BACnet: Real
LONWORKS: Fixed Point
Scalar - unsigned long
0–65,535 NA
BACnet
Compressor Select
This output network variable indicates the number of times the compressor motor of the compressor selected with Compressor
Select on page 43 has started. (I45)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 25 Present Value 85
Object Name
CompStarts
Compressor #2
This variable indicates the number of times the compressor 2 motor has started. (I106)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 92 Present Value 85
Object Name
Comp2Starts
Compressor #3
This variable indicates the number of times the compressor 3 motor has started. (I109)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 100 Present Value 85
Object Name
Comp3Starts
Compressor #4
This variable indicates the number of times the compressor 4 motor has started. (I112)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 108 Present Value 85
Object Name
Comp4Starts
LONWORKS
Variable Details
This output network variable indicates the number of times the compressor motor of the compressor selected with Compressor
Select on page 43. (I45)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoCompStarts Proprietary count 8 two bytes