ED 15062-7 • MICROTECH II CHILLER CONTROLLER 74 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Liquid Line Refrigerant Pressure
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the current liquid line refrigerant pressure. There is a separate
output for each compressor/circuit. See Compressor Select on page 43. (A38)
Measurement Units Data Type Valid Range Default Value
Pressure
BACnet: psi
LONWORKS: kPa
BACnet: Real
LONWORKS: Fixed-Point
Scalar signed long
BACnet: -22592–22591 psi
LONWORKS:
-3,276.8…3,276.7 kPa
NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 12 Present Value 85
Object Name
LiquidLinePress
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoLiquLinePress Proprietary press 30 two bytes