ED 15062-7 • MICROTECH II CHILLER CONTROLLER 90 www.DaikinApplied.com
alarms-baCneT
Fault Alarms, Multi-state Input Object
This BACnet object indicates the index number of Fault
Alarms in the present value property and the text of the alarm
message in the state text property. If the present value is zero,
no alarm has occurred. See Table 4 on page 91.
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 901 Present Value 85
Object Name
MSIFaultAlarm
Measurement Units Data Type Valid Range Default Value
NA NA Character String NA NA
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 901 State Text 110
Object Name
MSIFaultAlarm
Poll Singular
Alarm Digital Output
The Poll Singular method requires that one Binary Input object
in the BACnet Communication Module be polled for alarm
notication. This object indicates whether an alarm condition has
occurred. The operator interface displays the alarm text. (D3)
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 40 Present Value 85
Object Name
AlarmDigitalOutput
Property Values
0 = No Alarm
1 = Alarm