ED 15062-7 • MICROTECH II CHILLER CONTROLLER 64 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Evaporator Leaving Water Temperature for Compressor
Keypad Menu Path:
Menu
\View
\Comp
Measurement Units Data Type Valid Range Default Value
Temperature BACnet: °F BACnet: Real BACnet: -40°–244°F NA
BACnet
Compressor Select
This output network variable indicates the current temperature of the Evaporator leaving chilled water temperature of the
compressor selected with Compressor Select on page 43 (Centrifugals only). (A14)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 23 Present Value 85
Object Name
LvgEvapWaterTempComp
Compressor #2
This variable indicates the current temperature of the Evaporator leaving chilled water temperature of compressor 2. Not available
on all chiller models. (A87)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 68 Present Value 85
Object Name
Comp2EvapLvgWTmp

Table of Contents

Other manuals for Daikin MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech II and is the answer not in the manual?

Daikin MicroTech II Specifications

General IconGeneral
BrandDaikin
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals