ED 15062-7 • MICROTECH II CHILLER CONTROLLER 64 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Evaporator Leaving Water Temperature for Compressor
Keypad Menu Path:
Menu
\View
\Comp
Measurement Units Data Type Valid Range Default Value
Temperature BACnet: °F BACnet: Real BACnet: -40°–244°F NA
BACnet
Compressor Select
This output network variable indicates the current temperature of the Evaporator leaving chilled water temperature of the
compressor selected with Compressor Select on page 43 (Centrifugals only). (A14)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 23 Present Value 85
Object Name
LvgEvapWaterTempComp
Compressor #2
This variable indicates the current temperature of the Evaporator leaving chilled water temperature of compressor 2. Not available
on all chiller models. (A87)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 68 Present Value 85
Object Name
Comp2EvapLvgWTmp