ED 15062-7 • MICROTECH II CHILLER CONTROLLER 84 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Power Factor
Keypad Menu Path:
No Keypad Equivalent
Power factor is a read-only point that denes the cosine of the phase angle between the voltage applied
to a load and the current passing through the load. The power factor is assigned an analog value scaled
by 0.01 (i.e. a value of +95 corresponds to a power factor of 0.95). For a more detailed description of
power factor, see Application Guide AG 31-002, available on www.DaikinApplied.com
Measurement Units Data Type Valid Range Default Value
Power Factor Power Factor Real -99 - +100 N/A
BACnet
Compressor Select
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 53 Present Value 85
Object Name
PowerFactor
Compressor #2
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 78 Present Value 85
Object Name
Comp2PowerFactor
Compressor #3
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 97 Present Value 85
Object Name
Comp3PowerFactor
Compressor #4
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 105 Present Value 85
Object Name
Comp4PowerFactor
Compressor #5
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 113 Present Value 85
Object Name
Comp5PowerFactor
Compressor #6
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 119 Present Value 85
Object Name
Comp6PowerFactor
LONWORKS
No LONWORKS equivalent.

Table of Contents

Other manuals for Daikin MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech II and is the answer not in the manual?

Daikin MicroTech II Specifications

General IconGeneral
BrandDaikin
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals