ED 15062-7 • MICROTECH II CHILLER CONTROLLER 26 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Chiller Enable
Keypad Menu Path:
Menu
\Set
\Unit SP (1)
The Chiller Enable data point starts the chiller in a particular way. LONWORKS network variables can
set the default power-up and restart mode and start the chiller. The BACnet property is a commandable
property. Refer to the appropriate Operating Manual for suitable variable values. (D1)
Measurement Units Data Type Valid Range Default Value
Chiller State NA
BACnet: Enumerated
LONWORKS: structure
See Below See Below
BACnet
This read or read/write property enables (starts) the chiller to run if the operating conditions are satised, or disables (stops) the
chiller from running. When this property is read, it indicates the current operating state of the chiller.
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Value 5 41 Present Value 85
Object Name
ChillerEnable
Property Values
0 = Disable(Inactive)
1 = Enable(Active)
Default Value (Relinquish_Default)
0 = Request Chiller Off
LONWORKS
Input (nvi)
This input network variable enables (starts) the chiller to run if the operating conditions are satised, or disables (stops) the chiller
from running.
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT_ Index
nviChillerEnable Chiller Switch 95 two bytes NA NA
Structure
typedef struct {
unsigned value;
signed state;
} SNVT_switch;
Valid Range
Value Field unused
State Field 0 Request Chiller Off
1 Request Chiller Auto (run)
0xff Invalid