deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 29 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Chiller Location
Keypad Menu Path:
No Keypad Equivalent
This conguration network parameter provides a description of the location.
Measurement Units Data Type Valid Range Default Value
NA NA Structure
Any NUL terminated ASCII
string up to 31 bytes.
ASCII string of zeros + NUL
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT Index
nciLocation Chiller str_asc 36 31 bytes max SCPT_location 17
Structure
typedef struct {
unsigned char ascii[31];
} SNVT_str_asc;
Chiller Mode
Keypad Menu Path:
No Keypad Equivalent
This LONWORKS conguration network parameter establishes the default operating mode of the chiller,
unless the conguration parameter nciDefaults = 1 (See Default Values on page 59). If nciDefaults =
1, the default values are the values specied during manufacturing.
• Heat Mode
• Cool Mode (default)
• Ice Mode
Measurement Units Data Type Valid Range Default Value
HVAC Mode NA Unsigned Integer Enumerated See Below
LONWORKS
Default Value
3 = HVAC_COOL
The chiller object uses the conguration value of nciMode on power-up or loss of communication unless the conguration
parameter nciDefaults =1 (See Default Values on page 59).
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size SCPT Reference SCPT Index
nciMode Chiller hvac_mode 108 one byte SCPT_HVACmode 74