ED 15062-7 • MICROTECH II CHILLER CONTROLLER 72 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Ice Setpoint
Keypad Menu Path:
Menu
\Set
\Unit SPs (3)
The Ice Setpoint data point determines the temperature of the Leaving Chilled Water. LONWORKS
network variables set the operating Temperature. The BACnet property is a commandable property of a
Analog Output object. Refer to the appropriate Operation Manual for suitable variable values. (A30)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
Dependent on Chiller Mode
and Model
See below
BACnet
This commandable property sets the temperature of the Leaving Chilled Water. This level may be adjusted via an operator
workstation or other network device. When this property is read, it indicates the current value of the temperature of the Leaving
Chilled Water.
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Output 1 30 Present Value 85
Object Name
NetworkIceTempSetpoint
Default Value (Relinquish_Default) 25°F
LONWORKS
Input (nvi)
This input network variable provides the Ice setpoint of the Leaving Chilled Water when the chiller is operating in the Ice Mode.
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nviIceSpt Chiller temp_p 105 two bytes
Default Value -3.9°C