EasyManua.ls Logo

Daikin MicroTech II - Oil Sump Temperature

Daikin MicroTech II
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ED 15062-7 • MICROTECH II CHILLER CONTROLLER 82 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Oil Sump Temperature
Keypad Menu Path:
Menu
\View
\Comp (4)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Compressor Select
This output network variable indicates the current compressor oil sump temperature. There is a separate output for each
compressor. See Compressor Select on page 43. (A35)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 22 Present Value 85
Object Name
OilSumpTemp
Compressor #2
This output network variable indicates the current compressor oil sump temperature for compressor 2. Not available on all chiller
models. (A103)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 84 Present Value 85
Object Name
Comp2OilSumpTemp
LONWORKS
Variable Details
This output network variable indicates the current compressor oil sump temperature. There is a separate output for each
compressor. See Compressor Select on page 43. (A35)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoOilSumpTemp Proprietary temp_p 105 two bytes

Table of Contents

Other manuals for Daikin MicroTech II

Related product manuals