ED 15062-7 • MICROTECH II CHILLER CONTROLLER 40 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Compressor Power
Keypad Menu Path:
No Keypad Equivalent
Measurement Units Data Type Valid Range Default Value
Power kiloWatts
BACnet: Real
LONWORKS: Unsigned Long
0-6553.5 NA
BACnet
Compressor Select
This output network variable indicates the current power for the compressor motor of the compressor selected with Compressor
Select on page 43. (A27)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 54 Present Value 85
Object Name
Kilowatts
Compressor #2
This variable indicates the current power for the compressor motor of compressor 2. It is available via BACnet only.(A96)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 77 Present Value 85
Object Name
Comp2Kilowatts
Compressor #3
This variable indicates the current power for the compressor motor of compressor 3. It is available via BACnet only.(A108)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 96 Present Value 85
Object Name
Comp3Kilowatts
Compressor #4
This variable indicates the current power for the compressor motor of compressor 4. It is available via BACnet only.(A113)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 104 Present Value 85
Object Name
Comp4Kilowatts
Compressor #5
This variable indicates the current power for the compressor motor of compressor 5. It is available via BACnet only.(A118)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 112 Present Value 85
Object Name
Comp5Kilowatts