deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 39 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Compressor #6
This variable indicates the current motor current for compressor 6. (A123)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 116 Present Value 85
Object Name
Comp6CurrentPercent
LONWORKS
Variable Details
This output network variable indicates the current motor current for the compressor motor of the compressor selected with
Compressor Select on page 43. (A25)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoCompPercRLA Proprietary lev_percent 81 two bytes