ED 15062-7 • MICROTECH II CHILLER CONTROLLER 80 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Oil Feed Temperature
Keypad Menu Path:
Menu
\View
\Comp (4)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Compressor Select
This output network variable indicates the current compressor oil feed temperature. There is a separate output for each
compressor. See Compressor Select on page 43. (A34)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 21 Present Value 85
Object Name
OilFeedTemp
Compressor #2
This output network variable indicates the current compressor oil feed temperature for compressor 2. Not available on all chiller
models. (A102)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 83 Present Value 85
Object Name
Comp2OilFeedTemp
LONWORKS
Variable Details
This output network variable indicates the current compressor oil feed temperature. There is a separate output for each
compressor. See Compressor Select on page 43. (A34)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoOilFeedTemp Proprietary temp_p 105 two bytes

Table of Contents

Other manuals for Daikin MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech II and is the answer not in the manual?

Daikin MicroTech II Specifications

General IconGeneral
BrandDaikin
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals