ED 15062-7 • MICROTECH II CHILLER CONTROLLER 56 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Condenser Water Flow Rate
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the current condenser water ow rate. (A24)
Measurement Units Data Type Valid Range Default Value
Flow Volume
BACnet: GPM
LONWORKS: L/S
BACnet: Real
LONWORKS: Fixed Point
Scalar unsigned long
BACnet: 0–65,534
LONWORKS: 0–65,534
NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 50 Present Value 85
Object Name
CondWaterFlowRate
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoCondFlowRate Proprietary ow 15 two bytes