ED 15062-7 • MICROTECH II CHILLER CONTROLLER 76 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Maximum RPM
Keypad Menu Path:
No Keypad Equivalent
This output data point indicates the maximum (choke) RPM. This is the speed the Turbocor compressor
calculates above which the efciency of the compressor falls off. (I117 & I121)
Measurement Units Data Type Valid Range Default Value
Revolutions per Minute BACnet: RPM BACnet: Real BACnet: 0-32678 NA
BACnet
Compressor #1
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 55 Present Value 85
Object Name
Comp1MaxRPM
Compressor #2
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 59 Present Value 85
Object Name
Comp2MaxRPM
LONWORKS
No LONWORKS equivalent.
Maximum Send Time
Keypad Menu Path:
No Keypad Equivalent
This conguration network parameter controls the maximum period of time that expires before the
following network variables are transmitted.
• nvoChillerStat
• nvoActiveSetpt
• nvoActualCapacity
• nvoLvgChWTemp
• nvoLvgCndWTemp
• nvoEntCndWTemp
• nvoEntChWTemp
Measurement Units Data Type Valid Range Default Value
Elapsed Time seconds
BACnet: Unsigned Integer
LONWORKS: Fixed Point
Scalar - unsigned long
0–6553.4 sec 0 (no automatic update)
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT Index
nciMaxSendTime Chiller time_sec 107 two bytes SCPT_maxSendTime 49