deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 65 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Evaporator Pump Run Hours
Keypad Menu Path:
No Keypad Equivalent
NOTE: Value returned must be multiplied by 10 to give run hours.
Measurement Units Data Type Valid Range Default Value
Event Count NA
BACnet: Real
LONWORKS: Fixed-Point
unsigned long
0–65,535 NA
BACnet
Pump Select
This output network variable indicates the number of hours (x10) that the selected evaporator pump has been turned on. There is a
separate output for each pump. See Pump Select on page 85. (I47)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 27 Present Value 85
Object Name
EvapPumpOperHours
Pump #2
This variable indicates the number of hours (x10) for pump 2. Not available on all chiller models. (I105)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 89 Present Value 85
Object Name
EvapPmp2Hrs
LONWORKS
Variable Details
This output network variable indicates the number of hours (x10) that the selected evaporator pump has been turned on. See
Pump Select on page 85. (I47)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoEvapPumpHrs Proprietary count 8 two bytes