ED 15062-7 • MICROTECH II CHILLER CONTROLLER 52 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Condenser Leaving Water Temperature
Keypad Menu Path:
Menu
\View
\Unit Water
This output network variable indicates the current temperature of the leaving condenser water. (A8)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Variable Details
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 4 Present Value 85
Object Name
LvgCondWaterTemp
LONWORKS
Variable Details
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoLvgCndWTemp Chiller temp_p 105 two bytes