deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 73 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
IGV Percentage Open
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates current percent of vanes open for each compressor (0%=closed,
110%=full capacity-open) (I120 & I124)
Measurement Units Data Type Valid Range Default Value
Percent BACnet: % BACnet: Real BACnet: 0–110 NA
BACnet
Compressor #1
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 58 Present Value 85
Object Name
Comp1IGVPercentOpen
Compressor #2
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 62 Present Value 85
Object Name
Comp2IGVPercentOpen
LONWORKS
No LONWORKS equivalent.
Inverter Temperature
Keypad Menu Path:
No Keypad Equivalent
This output network variable the current drive temperature. There is one variable for each compressor.
(A86 & A106)
Measurement Units Data Type Valid Range Default Value
Temperature BACnet: °F BACnet: Real BACnet: 32.0–212.0°F NA
BACnet
Compressor #1
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 66 Present Value 85
Object Name
Comp1InverterTmp
Compressor #2
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 87 Present Value 85
Object Name
Comp2InverterTmp
LONWORKS
No LONWORKS equivalent.