deTaIled daTa PoInT InformaTIon
www.DaikinApplied.com 67 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Evaporator Saturated Refrigerant Temperature
Keypad Menu Path:
Menu
\Unit
\Refrigerant (1)
Measurement Units Data Type Valid Range Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Compressor Select
This output network variable indicates the current saturated refrigerant temperature in the evaporator. There is a separate output
for each compressor. See Compressor Select on page 43. (A16)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 14 Present Value 85
Object Name
EvapSatTemp
Compressor #2
This output network variable indicates the current saturated refrigerant temperature in the evaporator for compressor 2. (A89) Not
available on all chiller models.
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 70 Present Value 85
Object Name
Comp2EvapSatRTmp
LONWORKS
Variable Details
This output network variable indicates the current saturated refrigerant temperature in the evaporator. There is a separate output
for each compressor. See Compressor Select on page 43. (A16)
LONWORKS Name Prole SNVT Type SNVT Index SNVT Size
nvoSatEvapRefTemp Proprietary temp_p 105 two bytes