alarms-baCneT
www.DaikinApplied.com 89 ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Warning Alarms, Multi-state Input Object
This BACnet object indicates the index number of warning
alarms in the present value property and the text of the alarm
message in the state text property. If the present value is zero,
no alarm has occurred. See Table 4 on page 91.
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 902 Present Value 85
Object Name
MSIWarningAlarm
Measurement Units Data Type Valid Range Default Value
NA NA Character String NA NA
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 902 State Text 110
Object Name
MSIWarningAlarm
Problem Alarms, Multi-state Input Object
This BACnet object indicates the index number of problem
alarms in the present value property and the text of the alarm
message in the state text property. If the present value is zero,
no alarm has occurred. See Table 4.
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 900 Present Value 85
Object Name
MSIProblemAlarm
Measurement Units Data Type Valid Range Default Value
NA NA Character String NA NA
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 900 State Text 110
Object Name
MSIProblemAlarm