ED 15062-7 • MICROTECH II CHILLER CONTROLLER 46 www.DaikinApplied.com
deTaIled daTa PoInT InformaTIon
Compressor #4
This output network variable indicates the compressor status of the compressor 42. (I111)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 107 Present Value 85
Object Name
Comp4Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Compressor #5
This output network variable indicates the compressor status of the compressor 5. (I114)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 115 Present Value 85
Object Name
Comp5Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Compressor #6
This output network variable indicates the compressor status of the compressor 6. (I115)
Object Identier Property Identier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 121 Present Value 85
Object Name
Comp6Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
LONWORKS
No LONWORKS equivalent.

Table of Contents

Other manuals for Daikin MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech II and is the answer not in the manual?

Daikin MicroTech II Specifications

General IconGeneral
BrandDaikin
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals