Application Guide | iC2-Micro Frequency Converters
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Sum Sum both external and preset reference sources.
1 External/Preset Use either the preset or the external reference source. Shift
between external and preset via a command or a digital input.
P 5.5.3.6 Reference Site
Use this parameter to select which reference site to activate. To use the local reference in Local mode, or the remote reference in
Remote mode, select [0] Linked to Loc / Rem. To use the same reference in both Remote and Local modes, select [1] Remote or [2] Local
respectively.
Default value: 0 [Linked to Loc/Rem] Parameter type: Selection
Parameter
number:
313 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 Linked to Loc/Rem
1 Remote
2 Local
P 5.5.3.7 Reference 1 Source
Use this parameter to select the input for the 1st reference signal. The parameters P 5.5.3.7 Reference 1 Source, P 5.5.3.8 Reference 2
Source, and P 5.5.3.9 Reference 3 Source define up to 3 different reference signals. The sum of these reference signals defines the actual
reference.
Default value: 1 [Analog Input 33] Parameter type: Selection
Parameter
number:
315 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 No function
1 Analog Input 33
2 Analog Input 34
8 Frequency Input 18
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 159